3-19
Section 3 Specications
3-6-4 Analog output board (NA3AY02-MR)
(1) Specications
Item Specication
Type NA3AY02-MR
No. of output channels 2 channels
External load resistance Voltage output: 1k
W
to 1M
W
, Current output: 0 to 500
W
or less
Analog output range
0 to +10V
0 to 20mA
* Selectable by wiring of the terminal block.
Resolution 12 bits
Overall accuracy ±1%
Data type of digital output value INT type
Output period Synchronized with the scan of the main unit.
External wire connections 5-pole European-style terminal block (M2) x 1, Tightening torque: 0.2 N·m
Applicable wire size AWG#28-16 * Be sure to use shielded twisted pair cables.
Status indication None
Isolation method Not isolated
Occupied words 2 words
Internal current consumption 5V DC, 223mA
*1 Screw tightening torque for mounting the board on a main unit: 0.2 N·m
(2) Names
1) Terminal block
GND
VO0+
IO0+
VO1+
IO1+
<Signal assignment>
* For the detailed specications of and how to use the analog output board (Type: NA3AY02-MR), refer to the user’s manual
“Analog Unit (FEH527).”