3-24
Section 3 Specications
3-6-7 Resistance thermometer element input unit (NA0AX06-PT)
(1) Specications
Item Specication
Type NA0AX06-PT
No. of analog input channels 6 channels
Resolution 0.1°C or 1°C *1
Applicable resistance thermometer
element
Pt100, Pt1000 (JIS or DIN)
Temperature measurement range
Pt100: -200.0 to 850.0°C (-328.0 to 1562.0°F)
Pt1000: -200.0 to 600.0°C (-328.0 to 1112.0°F)
Overall accuracy ±1% *2
Resistance of input wiring 20Ω or less
Data type of A/D conversion value INT type
Sampling period
1 second (high speed) or 2 seconds (low speed)
(Collectively set for all channels by the program loader.)
Moving average
No moving average / 2 / 4 / 8 times
(Collectively set for all channels by the program loader.)
External wire connections 8-pole terminal block (M3) x 2, Tightening torque: 0.59 to 0.78 N·m
Applicable wire size AWG#22-18 * Be sure to use shielded twisted pair cables.
Status indication 5V power supply display, ON when normal (red)
Isolation method Not isolated
Occupied words 6 words
External power supply 24V DC, 16mA *Wiring length: 10m or less
Internal current consumption 5V DC, 32mA
Dimensions 40 (W) x 90 (H) x 80 (D) (mm)
*1 The resolution is determined by the setting of the “sampling period” in the parameter.
When the resolution is 1°C: Set to “high speed.”
When the resolution is 0.1°C: Set to “low speed.”
*2 The overall accuracy is the specication for when noise described in “Electrical service conditions” is not applied.
If noise is applied, the overall accuracy may exceed the above specication.
(2) Names
<Signal assignment>
2) Terminal block
1) Status indication LED
Nameplate
Expansion connector (IN)
Expansion connector (OUT)
2) Terminal block
* For the detailed specications of and how to use the resistance thermometer element input unit (Type: NA0AX06-PT), refer to
the user’s manual “Analog Unit (FEH527).”

Table of Contents

Related product manuals