3-16
Section 3 Specications
3-6-2 Analog output unit (NA0AY02-MR)
(1) Specications
Item Specication
Type NA0AY02-MR
No. of output channels 2 channels
External load resistance Voltage output: 500
W
to 1 M
W
, Current output: 0 to 500
W
or less
Analog output range
-10 to +10V, -5 to +5V, 0 to 10V, 0 to 5V
-20 to 20mA, -10 to 10mA, 0 to 20mA, 0 to 10mA
(Collectively set for all channels by the jumper pin in the unit)
Resolution 14 bits
Overall accuracy ±1%
Data type of digital output value INT type
Output period Synchronized with the scan of the main unit.
External wire connections 8-pole terminal block (M3) x 2, Tightening torque: 0.59 to 0.78 N·m
Applicable wire size AWG#22-18 * Be sure to use shielded twisted pair cables.
Status indication 5V power supply display, ON when normal (red)
Isolation method Not isolated
Occupied words 2 words
External power supply 24V DC, 90mA *Wiring length: 10m or less
Internal current consumption 5V DC, 33mA
Dimensions 40 (W) x 90 (H) x 80 (D) (mm)
(2) Names
NA0AY02-MR
Terminal block
Status indication LED
Expansion connector (IN)
Expansion connector (OUT)
Terminal block
<Signal assignment>
㻺㻭㻜㻭㼅㻜㻞㻙㻹㻾
* For the detailed specications of and how to use the analog output unit (Type: NA0AY02-MR), refer to the user’s manual “Analog
Unit (FEH527).”