EasyManua.ls Logo

Fuji Electric MICREX-SX series SPF - Relay Output Specifications; Specifications

Fuji Electric MICREX-SX series SPF
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-10
Section 3 Specications
3-5-2 Relay output specications
(1) Specications
Item Specication
Output power
supply conditions
Rated voltage
(tolerance)
250V AC or less / 30V DC or less
Output circuit
characteristic
Output type Relay output
Max. load current
2A/common, 4A/common (resistive load)
80VA (AC) / 24VA (DC) (inductive load)
Response
time
ON to OFF 10ms or less
OFF to ON 10ms or less
Min. make/break current 5V DC, 2mA
Output element Relay output
On/off times Max. 1800 times/hour
Output protection
method
Built-in fuse None
Surge absorption circuit None
Others None
External wire connections Terminal block (M3 screw)
Output indication LED indicator turns on when input is “ON” and turns off when output is “OFF”.
Isolation method Relay
Dielectric strength 1500V AC 1 minute (between output terminals and frame ground)
Insulation resistance
10MΩ or more with 500V DC megger
(between output terminals and frame ground)
Derating condition Specied (Note 1)
Notes:
1) See “3-9 Temperature derating of main unit.”