4-3
Section 4 Installation and Wiring
4-1-3 Control panel mounting (protection against noise)
The SPF series products are especially immure to noise pickup. However, it is always recommended to take the following
measures to further enhance system reliability.
erusaemretnuoCesion fo esuaC.oN
1 Noise via power-supply terminals
Lightning surge
Internal surge (switching surge)
1) An isolation transformer should be used.
.desu eb dluohs retlif esion A esion ycneuqerf-hgiH2
Twisted pair wires should be used between the noise
filter and power-supply terminals of the PLC.
.sdnuorg laudividni mumitpo swohs erugif gniwollof ehT enil dnuorg nommoc aiv tupni esioN3
4 Noise via ground of the secondary coils of a transformer The secondary side of the isolation transformer should
not be grounded as shown in the above ltem 1.
2) An isolation transformer should be used.
PLC
Electrostatic shielding
(to reduce the stray capacitance
between the primary and
secondary coils)
Device
Cabinet
Surge absorber
(FUJI Z-trap)
Power
supply
Example: FUJI FHF-type
power filter
PLC
Noise filter
Other device
Other device
PLC
Common ground must not be used.
Other device
Other device
Type D (Class 3) grounding
(ground resistance of
100 or less)
PLC