3-15
Section 3 Specications
3-6 Analog Unit/Board Specications
3-6-1 Analog input unit (NA0AX06-MR)
(1) Specications
Item Specication
Type NA0AX06-MR
No. of input channels 6 channels
Input impedance Voltage: 63.2 k
W
, Current: 250
W
Maximum allowable input Voltage: ±15V, Current: 30mA
Input range
-10 to +10V, -5 to +5V, 0 to 10V, 0 to 5V
-20 to 20mA, -10 to 10mA, 0 to 20mA, 0 to 10mA
(Collectively set for all channels by the jumper pin in the unit)
Resolution 12 bits or 14 bits (Set for individual channels by the program loader.)
Overall accuracy ±1% *1
A/D conversion value INT type
Sampling period Synchronized with the scan of the main unit.
Moving average 1 to 16 times (Set for individual channels by the program loader.)
External wire connections 8-pole terminal block (M3) x 2, Tightening torque: 0.59 to 0.78 N·m
Applicable wire size AWG#22-18 * Be sure to use shielded twisted pair cables.
Status indication 5V power supply display, ON when normal (red)
Isolation method Not isolated
Occupied words 6 words
External power supply 24V DC, 53mA *Wiring length: 10m or less
Internal current consumption 5V DC, 25mA
Dimensions 40 (W) x 90 (H) x 80 (D) (mm)
Terminal block
Terminal block
Status indication LED
Expansion connector (IN)
Expansion connector (OUT)
<Signal assignment>
*1 The overall accuracy is the specication for when noise described in “Electrical service conditions” is not applied.
If noise is applied, the overall accuracy may exceed the above specication.
(2) Names
* For the detailed specications of and how to use the analog input unit (Type: NA0AX06-MR), refer to the user’s manual “Analog
Unit (FEH527).”