Section 4 Software Interface
4-1 Analog Input Module
<Conversion enable/disable, the unit of digital output value> (offset address +2)
Bit Flag name Descrip tion
0to7 Unused
8 C hannel 1 Conversion enable/disable OFF: E nable,
ON: Disable
9 C hannel 2 Conversion enable/disable
10 C hannel 3 Conversion enable/disable
11 Channel 4 Conversion enable/disable
12 C hannel 5 Conversion enable/disable
13 C hannel 6 Conversion enable/disable
14 C hannel 7 Conversion enable/disable
15 C hannel 8 Conversion enable/disable
<Input range setting> (Offset address +3)
Bit Flag name
Descrip tion
0(L)
Channel 1 Input range
ThesetrangeisindictedbyacombinationofON/OFFstatuso
two bits.
1(H)
2(L)
Channel 2 Input range
3(H)
4(L)
Channel 3 Input range
5(H)
6(L)
Channel 4 Input range
7(H)
8(L)
Channel 5 Input range
9(H)
10 (L)
Channel 6 Input range
11 (H)
12 (L)
Channel 7 Input range
13 (H)
14 (L)
Channel 8 Input range
15 (H)
<NP1AXH8V-MR>
H L
OFF OFF : -10 to 10 V
OFF ON : 0 to 10 V
ON OFF : 0 to 5 V
ON ON : 1 to 5 V
<NP1AXH8I-MR>
H L
OFF OFF : 4 to 20 mA
OFF ON : 0 to 20 mA
ON OFF : -20 to 20 mA
ON ON : 4 to 20 mA