4-29
Section 4 Software Interface
4-3 Analog Input/Output Module
(4) Parameter type setting status register (offset address +1)
This register stores the information of what parameter is now being written or read by the module.
* When using D300win, assign a WORD type variable to this register. If you access by the bit, assign a BOOL type variable to
each bit.
15(F) 078
+1
Channel No. Parameter type
Bit Flag name Descrip tion
0 Operation parameter read mode ON: Operation parameter read mode (all channels in a batch)
1 Scali ng parameter read mode ON: Scaling parameter read mode (indivi dual channel)
2 Operation range parameter read mode ON: Operati on range parameter read mode (all channels in a batch)
3 Unused
4 Operation parameter wri te mode ON: Operation parameter wri te mode (all channels i n a batch)
5 Scaling parameter write mode ON: Scaling parameter write mode (indi vi dual channel)
6 Operation range parameter write mode ON: Operation range parameter write mode (all channels i n a batch)
7 Offset/gain adjustment mode ON: Offset/gain adjustment mode (indivi dual channel)
8 C hannel 1 In "scaling parameter read mode" or "scaling parameter write mode",
one of bits 8 to 15 is set ON to indicate which channel is now being se
t
or read out.
9 Channel 2
10 Channel 3
11 Channel 4
12 Channel 5
13 Channel 6
14 Unused
15 Unused
(5) Parameter read data register (offset address +2 and +3)
In “operation parameter read mode”, “scaling parameter read mode”, “operation range parameter read mode”or “offset/gain
adjustment mode”, the content of the setting for the corresponding mode is stored in this register.
1) When operation parameter read mode is activated
15(F)
13(D)
0
+2
+3
Unused
Unused
Unused
Conversion
(output)
enable/disable
Conversion
(output)
enable/disable OFF:
(Output)
enable, ON:
(Output)
disable
Moving average execution times
Moving average execution times H/L = OFF/OFF: Once, OFF/ON: Twice, ON/OFF: 4 times, ON/ON: 8 times
78
CH6
CH4 CH3 CH2
CH1
CH5 CH4 CH3 CH2 CH1
13(D)
12(C)
11(B)10(A)
98
7 6 5 4 3 2 1 0
H L H L H L H L
* When using D300win, assign WORD type variables to these registers. If you access by the bit, assign a BOOL type variable
to each bit.