4-31
Section 4 Software Interface
4-3 Analog Input/Output Module
(6) Parameter setting request (offset address +4)
When parameters are set, input a value in the range from “30000” to “32767” to this register. Make sure that the status register
(offset address +0) is “30001” and then set parameters.
(7) Parameter type setting register (offset address +5)
Parameter type and channel number for reading/writing parameters are set in this register.
* When using D300win, assign a WORD type variable to this register. If you access by the bit, assign a BOOL type variable to
each bit.
15(F) 078
+5
Channel No. Parameter type
Bit Flag name Descrip tion
0 Operation parameter read mode ON: Operation parameter read mode (all channels in a batch)
1 Scali ng parameter read mode ON: Scaling parameter read mode (indivi dual channel)
2 Operation range parameter read mode ON: Operati on range parameter read mode (all channels in a batch)
3 Unused
4 Operation parameter wri te mode ON: Operation parameter wri te mode (all channels i n a batch)
5 Scaling parameter write mode ON: Scaling parameter write mode (indi vi dual channel)
6 Operation range parameter write mode ON: Operation range parameter write mode (all channels i n a batch)
7 Offset/gain adjustment mode ON: Offset/gain adjustment mode (indivi dual channel)
8 C hannel 1 In "scaling parameter read mode", "scaling parameter wri te mode" or
"offset/gain adjustment mode", one of bits 8 to 15 is set ON to specify a
channel for which parameters are to be set.
9 Channel 2
10 Channel 3
11 Channel 4
12 Channel 5
13 Channel 6
14 Unused
15 Unused