Table 6: Allen Bradley CSP (PCCC) Specifications
Read Services
PLC5 Read (DF1 protocol typed read, 0x68) ,
PLC5 Word Range Read (DF1 protocol word range read, 0x01),
SLC Read (DF1 protocol protected typed logical read
with three address fields, 0xA2)
Write Services
PLC5 Write (DF1 protocol typed write, 0x67) ,
PLC5 Word Range Read (DF1 protocol word range write, 0x00),
SLC Read (DF1 protocol protected typed logical write
with three address fields, 0xAA)
Logical Binary Addressing
240 bytes (120 16-bit Integers)
240 bytes (120 16-bit Integers)
Table 7: BACnet/IP Specifications
Standard Device Profile
(Annex L)
BACnet Application Specific Controller (B-ASC)
BACnet Interoperability Building
Blocks (BIBB)
ReadProperty-B (DS-RP-B), ReadPropertyMultiple-B (DS-RPM-B),
WriteProperty-B (DW-WP-B), Dynamic Device Binding-B (DM-
DDB-B), Dynamic object Binding-B (DM-DOB-B)
Object Types
Analog Output, Analog Input, Analog Value, Binary Output, Binary
Input, Binary Value, Multi-state Output, Multi-state Input, Multi-state
47808 (0xBAC0, configurable)
Min 160us, Typical less than 1ms