6-18 MHT258a (Engl.)
6.3.2 Rewriting inhibit
Parameter rewriting on the keypad panel can be prohibited.
System parameter 94
Para. Name Setting range Initial value Change
94 Parameter rewriting inhibit 0: Rewriting allowed
1: Rewriting inhibit
0Always
Setting Parameter editing
0: Rewriting allowed Enable
1: Rewriting inhibit Disabled
Even if “1 : Rewriting inhibit” is selected, only the system para. 94 is rewritable.
Remark : Rewrite operation can be restricted by the control input terminal. See 5-5-2 Edit permit on.
6.3.3 Terminal function assignment
Various functions can be assigned to the control input terminals and output terminals.
System parameter 1 to 8
Para. Name Setting range Initial value Change
01 CONT1 signal assignment 0 to 56 (in increments of 1) 1 Power
02 CONT2 signal assignment 0 to 56 (in increments of 1) 2 Power
03 CONT3 signal assignment 0 to 56 (in increments of 1) 3 Power
04 CONT4 signal assignment 0 to 56 (in increments of 1) 11 Power
05 CONT5 signal assignment 0 to 56 (in increments of 1) 51 Power
06 CONT6 signal assignment 0 to 56 (in increments of 1) 52 Power
07 CONT7 signal assignment 0 to 56 (in increments of 1) 27 Power
08 CONT8 signal assignment 0 to 56 (in increments of 1) 37 Power
System parameter 31 to 35
Para. Name Setting range Initial value Change
31 OUT1 signal assignment 0 to 41 (in increments of 1) 1 Power
32 OUT2 signal assignment 0 to 41 (in increments of 1) 28 Power
33 OUT3 signal assignment 0 to 41 (in increments of 1) 24 Power
34 OUT4 signal assignment 0 to 41 (in increments of 1) 0 Power
35 OUT5 signal assignment 0 to 41 (in increments of 1) 0 Power