MHT258a (Engl.)3-3
(c) Perpendicularity of mounting face of flange to shaft for flange-mounted motor
The indicator is fitted rigidly on the shaft extension.
[unit : mm]
(a) (b) (c)
Flange-mounted Flange-mounted Flange-mounted
0.02 0.06 0.08
(7) Stress of Cable
Strain relief and mechanical protection for the connection cables and connector has to be provide in final installation.
3.2 Amplifier
(1) Installation environment
(a) Ambient climatic conditions
Ambient conditions Amplifier Motor
Temperature 20 to 80[] 10 to 70[]
Humidity 90[%] RH max.
In transportation and storage
(*1)
Air pressure 86 to 106 [kPa]
Temperature 10 to 55[] 10 to 40[]
Humidity 90[%] RH max.
Control rooms and equipment rooms
(*1)
Air pressure 86 to 106 [kPa]
Install location (*2) For indoors
(*1) Free from condensation, no condensation, no formation of ice
(*2) Site-altitude should be 1000[m] and below.
(b) Avoid use under the following conditions.
(i) Location near oil, steam or corrosive gas
(ii) Location where strong electric or magnetic field exists
(iii) Accommodation in the same panel together with high voltage (2[kV] or higher) equipment
(iv) Sharing of the same power supply with the equipment which generates large noise.
(v) In vacuum
(vi) In explosive atmosphere
(vii) Under acceleration vibration