(H codes continued)
Code
Name
Data setting range
Incre-
ment
Unit
Change
when
running
Data
c
opying
De
fault
setting
H50
Non-linear V/f Pattern 1
(Frequency)
(Voltage)
0.0 (Cancel), 0.1 to 400.0
0.1
Hz
N
Y
0.0
H51 0 to 240: Output an AVR-controlled voltage
(for 200 V class series)
0 to 500: Output an AVR-controlled voltage
(for 400 V class series)
1 V N Y2
0.0
H52 Non-linear V/f Pattern 2
(Frequency)
(Voltage)
0.0 (Cancel), 0.1 to 400.0 0.1 Hz N Y 0.0
H53
0 to 240: Output an AVR-controlled voltage
(for 200 V class series)
0 to 500: Output an AVR-controlled voltage
(for 400 V class series)
1
V
N
Y2
0
H54 ACC/DEC Time
(Jogging operation)
0.00 to 3600 0.01 s Y Y 6.00
H61
UP/DOWN Control
(Initial frequency setting)
0: 0.00
1: Last UP/DOWN command value on
releasing a run command
N
Y
1
H63
Low Limiter
(Mode selection)
(Lower limiting
frequency)
0: Limit by F16 (Frequency limiter: Low)
and continue to run
1: If the output frequency lowers below the
one limited by F16 (Frequency limiter:
Low), decelerate to stop the motor.
Y
Y
0
H64
0.0 (Depends on F16 (Frequency limiter:
Low))
0.1 to 60.0
0.1
Hz
Y
Y
2.0
H69
Automatic Deceleration
(Anti-regenerativ
e
control)
(Mode selection)
0: Disable
1: Enable (Lengthen the deceleration time
to three times the specified time under
voltage limiting control.) (Compatible with
the original FVR-Micro
FVR
AS1S-
)
4: Enable (Torque limit control: Disable
force-to-stop processing.)
Y
Y
0
H70 Overload Prevention
Control
0.00: Follow deceleration time specified by
F08/E11
0.01 to 100.0, 999 (Cancel)
0.01 Hz/s
Y Y 999
H71 Deceleration
Characteristics
0: Disable
1: Enable
Y Y 0
H76
Automatic Deceleration
(Frequency increment
limit for braking)
0.0 to 400.0
0.1
Hz
Y
Y
5.0
H78
Maintenance Interval *1
0: Disable,
1 to 9999 (in units of 10 hours)
1
Y
N
8760
H79 Preset Startup Count for
Maintenance *1
0000: Disable,
0001 to FFFF (hex.)
1 Y N 0000
H80
Output Current
Fluctuation Damping
Gain for Motor 1
0.00 to 0.40
0.01
Y
Y
0.20
5-13