11. Safety devices
Indoor unit
type
Model name PCB* fuse Fan motor thermal protector
Terminal
thermal
fuse
Float
switch
Compact
cassette
AUXG07KVLA
250 V, 5 A
Activate: 100 ±10°C
Fan motor stop
Reset: 95 ±10°C
Fan motor restart
AUXG09KVLA
AUXG12KVLA
AUXG14KVLA
Mini duct
ARXG07KSLAP Activate: 135 ±15°C
Fan motor stop
Reset: 115 ±15°C
Fan motor restart
ARXG09KSLAP
ARXG12KSLAP
ARXG14KSLAP
Slim duct
ARXG07KLLAP
Activate: 135 ±15°C
Fan motor stop
Reset: 105 ±15°C
Fan motor restart
ARXG09KLLAP Activate: 135 ±15°C
Fan motor stop
Reset: 115 ±15°C
Fan motor restart
ARXG12KLLAP
ARXG14KLLAP
Wall mounted
ASYG07KGTB
250 V, 3.15 A
Activate: More than 95°C
Fan motor speed down
Reset: 95°C or less
Fan motor speed recover
102°C Off
ASYG09KGTB
ASYG12KGTB Activate: 125 ±10°C
Fan motor stop
Reset: 100 ±10°C
Fan motor restart
ASYG14KGTB
ASYG07KGTE Activate: More than 95°C
Fan motor speed down
Reset: 95°C or less
Fan motor speed recover
ASYG09KGTE
ASYG12KGTE Activate: 125 ±10°C
Fan motor stop
Reset: 100 ±10°C
Fan motor restart
ASYG14KGTE
ASYG07KGTF Activate: More than 95°C
Fan motor speed down
Reset: 95°C or less
Fan motor speed recover
ASYG09KGTF
ASYG12KGTF Activate: 125 ±10°C
Fan motor stop
Reset: 100 ±10°C
Fan motor restart
ASYG14KGTF
ASYG07KMTB Activate: More than 95°C
Fan motor speed down
Reset: 95°C or less
Fan motor speed recover
ASYG09KMTB
ASYG12KMTB
ASYG14KMTB
Activate: 125 ±10°C
Fan motor stop
Reset: 100 ±10°C
Fan motor restart