External input
With using external input function, some functions on this product can be controlled from an external
device.
“Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m.
The wire connection should be separate from the power cable line.
Indoor unit functions such as Operation/Stop can be done by using indoor unit terminals.
1
2

Terminal
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
¢
External output
Use an external output cable with appropriate external dimension, depending on the number of ca-
bles to be installed.
A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m.
Output voltage: High DC 12 V ± 2 V, Low 0 V.
Permissible current: 50 mA
For details, refer to "Combination of external input and output" on page 126.
When indicator, etc. are connected directly
Example: Function setting 60 is set to "00"
1
2
CN47
LED
PCB
Resistor
Connected unit
+
-
When connecting with a device equipped with a power supply
Example: Function setting 60 is set to "00"
1
2
Connected device
CN47
PCB
Connected unit Relay
(Operation status)
-
+
- 125 -
12-1. Compact cassette, Mini duct, and Slim duct types 12. External input and output
2-UNIT
MULTI-SPLIT TYPE
2-UNIT
MULTI-SPLIT TYPE

Table of Contents

Other manuals for Fujitsu AOYG14KBTA2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOYG14KBTA2 and is the answer not in the manual?

Fujitsu AOYG14KBTA2 Specifications

General IconGeneral
BrandFujitsu
ModelAOYG14KBTA2
CategoryAir Conditioner
LanguageEnglish

Related product manuals