Control output function
Operation/Stop status
Function setting /
Rotary SW on
External Input
and Output PCB
External output
Output
signal
Command
60-00 / 1
Output of indoor unit CN47
Off → On Operation
60-00 / 2
On → Off Stop
60-00 / 1
External Input and
Output PCB
CN310
Off → On Operation
60-09 / B
60-10 / C
On → Off Stop
60-11 / D
The output is low when the unit is stopped.
Operation
Stop
On
Off
CN47
On
Off
CN310
Indoor unit
Error status
Function setting /
Rotary SW on
External Input
and Output PCB
External output
Output
signal
Command
60-09 / B Output of indoor unit CN47
Off → On Error
On → Off Normal
60-00 / 2
External Input and
Output PCB
CN310
Off → On Error
On → Off Normal
60-00 / 1
CN311
Off → On Error
60-10 / C
On → Off Normal
60-11 / D CN312
Off → On Error
On → Off Normal
The output is ON when an error is generated for the indoor unit.
Error
Normal
On
Off
CN47
On
Off
CN310―312
Indoor unit
- 156 -