Control output function
Operation/Stop status
Mode Function setting External output
Output
signal
Command
0 60-00
Output of indoor unit
CN15
Low → High Operation
High → Low Stop
0 60-00 CN20
Off → On Operation
On → Off Stop
The output is low when the unit is stopped.
Operation
Stop
High
Low
CN15
On
Off
CN20
Indoor unit
Error status
Mode Function setting External output
Output
signal
Command
9 60-09
Output of indoor unit
CN15
Low → High Error
High → Low Normal
0 60-00 CN21
Off → On Error
On → Off Normal
The output is ON when an error is generated for the indoor unit.
Error
Normal
High
Low
CN15
On
Off
CN21
Indoor unit
- 163 -