2. Pipe design
2-1. Important items when using refrigerant (R410A)
Refrigerant piping material and wall thickness
It is necessary to use seamless copper tubes for refrigerant use. Thickness of tubes are shown in
table below.
Nominal diameter in 1/4 3/8 1/2 5/8 3/4 7/8 1-1/8
Outside diameter mm 6.35 9.52 12.70 15.88 19.05 22.22 28.58
Material
JIS H3300 C1220T-O or equivalent*
1
JIS H3300 C1220T-H
or equivalent*
2
Wall thickness*
3
mm 0.8 1.0 1.2 1.0
*1: Allowable tensile stress ≥ 33 N/mm
2
*2: Allowable tensile stress ≥ 61 N/mm
2
*3: Endurance pressure of the pipes: 4.2 MPa
Select the pipe size in accordance with local rules.
Lubricant
Refrigerant R410A (Mixed refrigerant)
Lubricant Synthetic oil
Tools
R410A work requires a number of special tools. Since the tools (with * symbol) for R22 work can-
not be used for R410A, prepare them beforehand.
Tool name Process and application
Pipe cutter Pipe cutting
Refrigerant piping work
Flaring tool* Pipe flaring work
Torque wrench* Flare nut connection
Expander Expansion at pipe connection
Pipe bender Pipe bending work
Nitrogen gas Pipe interior oxidation prevention
Air tightness test
Welder Pipe brazing
Gauge manifold* Vacuum evacuation and
refrigerant charging operation
check
Air tightness test ~ Refrigerant
additional charging
Charging hose*
Vacuum pump (with adapter)* Vacuum drying
Electronic scale for refrigerant
charging
Refrigerant additional charging
Gas leak tester* Gas leakage test
*: For details, refer to the service manual.
- 179 -
2-1. Important items when using refrigerant (R410A) 2. Pipe design
SYSTEM
DESIGN
SYSTEM
DESIGN

Table of Contents

Other manuals for Fujitsu ARYG36LMLE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARYG36LMLE and is the answer not in the manual?

Fujitsu ARYG36LMLE Specifications

General IconGeneral
TypeAir conditioner indoor unit
Multi-split-
Hose diameter- mm
Product colorBlack, Stainless steel
Dehumidifying capacity- l/h
Air conditioner functionsCooling, Dehumidifying, Heating
Refrigerating medium weight- g
Cooling capacity in watts (nominal)- W
Operating temperature (cooling) (T-T)- °C
Current20 A
AC input voltage230 V
Current (cooling)18.5 A
AC input frequency50 Hz
Design load (cooling)- kW
Annual energy consumption (cooling)- kWh
Indoor unit typeCassette
Indoor unit depth700 mm
Indoor unit width1135 mm
Indoor unit height270 mm
Indoor unit weight40000 g
Cooling airflow (indoor unit)1900 m³/h
Indoor unit noise level (high speed)39 dB
Outdoor unit noise level- dB

Related product manuals