En-10
A. For solid core wiring
(1) To connect the electrical terminal, follow the below
diagram and connect after looping it around the end of the
cable.
(2) Usethespeciedcables,connectthemsecurely,and
fasten them so that there is no stress placed on the
terminals.
(3) Use an appropriate screwdriver to tighten the terminal
screws.Donotuseascrewdriverthatistoosmall,
otherwise, the screw heads may be damaged and prevent
the screws from being properly tightened.
(4) Donottightentheterminalscrewstoomuch,otherwise,
the screws may break.
(5) See the table for the terminal screw tightening torques.
(6) Pleasedonotxtwopowersupplycableswithonescrew.
Strip 25 mm
Loop
Screw with
special washer
Cable
Cable end (Loop)
Terminal block
Screw with
special
washer
Cable end
(Loop)
Cable
WARNING
•When using solid core cables, do not use the ring
terminal. If you use the solid core cables with the ring
terminal, the ring terminals pressure bonding may
malfunction and cause the cables to abnormally heat up.
B. For strand wiring
(1) Use ring terminals with insulating sleeves as shown in the
gurebelowtoconnecttotheterminalblock.
(2) Securely clamp the ring terminals to the cables using an
appropriate tool so that the cables do not come loose.
(3) Use the specified cables, connect them securely, and
fasten them so that there is no stress placed on the
terminals.
(4) Use an appropriate screwdriver to tighten the terminal
screws. Do not use a screwdriver that is too small,
otherwise, the screw heads may be damaged and prevent
the screws from being properly tightened.
(5) Do nottighten the terminal screws too much, otherwise,
the screws may break.
(6) See the table for the terminal screw tightening torques.
(7) Pleasedonotxtwopowersupplycableswithonescrew.
]1
6.1. Electrical requirement
Voltage rating
230 V
Operating range
198 - 264 V
Recom-
mended cable
size (mm
2
)
Cable type Remark
Power
supply cable
2.5
Type245 IEC57
or equivalent
1ø 50 Hz
198 - 264 V
2 Cable + ground
Transmission
cable
0.33
LONWORKS
compatible cable
22AWG
LEVEL 4 (NEMA)
non-polar 2 core,
twisted pair solid
core diameter
0.65 mm
Remote
control cable
0.33
Sheathed
PVC cable*
Polar 3 core
Twisted pair
*: Useshieldedcableinaccordancewithlocalrulesfor
remote control cable.
]1
6.2. Wiring method
(EXAMPLE)
POWER SUPPLY
OUTDOORUNIT
BREAKER
POWER SUPPLY
TRANSMISSION
TRANSMISSION
POWER
SUPPLY
POWER
SUPPLY
REMOTE
CONTROL UNIT
(MASTER)
REMOTE
CONTROL UNIT
POWER
SUPPLY
REMOTE
CONTROL
TRANSMISSION TRANSMISSION
POWER
SUPPLY
POWER
SUPPLY
REMOTE
CONTROL
REMOTE
CONTROL
INDOORUNIT
POWER
SUPPLY
REMOTE
CONTROL UNIT
(SLAVE)
INDOORUNIT
INDOORUNIT
BREAKER BREAKER BREAKER
]1
6.3. Unit wiring
• Beforeattachingthecabletoterminalblock.
6.3.1. Power supply cable
Power supply cable
30 mm
90 mm
Earth cable
9371057033-02_IM_en.indd 10 2/20/2009 3:13:33 PM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASYA18L and is the answer not in the manual?

Fujitsu ASYA18L Specifications

General IconGeneral
BrandFujitsu
ModelASYA18L
CategoryAir Conditioner
LanguageEnglish

Related product manuals