Table 2 Efficiency and Power Factor of the Power Supply Unit (ETERNUS DX100 S4)
Component name
80PLUS
®
Efficiency
Power fac-
tor
Output
20% (*1) 50% (*1) 100% (*1) 50% (*1)
Controller enclosure 2.5" type GOLD (*2) 89.3% 92.5% 90.2% 0.975 Multiple output
3.5" type
Drive enclosure 2.5" type 89.3% 92.5% 90.2% 0.975
3.5" type
High-den-
sity type
90.1% 92.4% 90.3% 0.975
*1: Indicates the rated load against the rated output of the PSU.
*2: 80PLUS
®
GOLD certified power supply units are used. 80PLUS
®
is a power saving program for electrical
equipment promoted by the 80PLUS
®
program.
ETERNUS DX100 S3
The following table shows the installation specifications of the ETERNUS DX100 S3.
Table 3
ETERNUS DX100 S3 Installation Specifications
Item ETERNUS DX100 S3
Dimensions
(W ´ D ´ H)
Controller enclosure 2.5" type
482 ´ 645 ´
88mm (2U)
3.5" type
482 ´ 670 ´
88mm (2U)
Drive enclosure 2.5" type
482 ´ 540 ´ 88mm (2U)
3.5" type
482 ´ 560 ´ 88mm (2U)
High-density type
482 ´ 980 ´
176mm (4U)
Power distribution unit (*1) 1U
435 ´ 148 ´ 38mm (*2),
482 ´ 111 ´ 44mm (*3)
2U (*4)
(485 ´
280 ´ 43mm) ´ 2 (*5),
(485 ´ 123 ´ 44mm) ´ 2 (*6)
Maximum weight
(*7)
Controller enclosure 2.5" type 35kg
3.5" type 35kg
Drive enclosure 2.5" type 35kg
3.5" type 35kg
High-density type 100kg
Power distribution unit (*1) 1U 2.0kg (*2),
2.5kg (*3)
2U (*4)
(6.0kg) ´
2 (*5),
(3.0kg) ´ 2 (*6)
Power Voltage AC 100 – 120V, AC 200 – 240V
Phase Single
Frequency 50Hz/60Hz
1. ETERNUS DX Installation
Installation Specifications
10
FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems
Site Planning Guide
Copyright 2021 FUJITSU LIMITED
P3AM-7632-18ENZ0