Power Distribution Units (1U)
(Only for Regions other than the EMEIA, Central American,
and Caribbean Regions)
Two types (Figure 10 and Figure 11) of 1U power distribution units with different specifications are provided.
•
Power distribution unit (AC8A/200-240V, 1U, 4 outlets, 2 inlets)
There are four outlets and two inlets.
Figure 10 Power Distribution Units (AC8A/200-240V, 1U, 4 Outlets, 2 Inlets)
Table 13 Specifications for Power Distribution Units (AC8A/200-240V, 1U, 4 Outlets, 2 Inlets)
Outlet Inlet
Voltage rating/current
rating
Socket type
(Socket)
Plug type
Socket type
(Socket)
Cable length
IEC60320 C13
NEMA L6-15P NEMA L6-15R 4.0m Rating: 250V 10A
(Normal usage rating:
8A)
•
Power distribution unit (AC24A/200-240V, 1U, 4 outlets, 1 inlet)
There are four outlets and one inlet.
Figure 11 Power Distribution Units (AC24A/200-240V, 1U, 4 Outlets, 1 Inlet)
Table 14 Specifications for Power Distribution Units (AC24A/200-240V, 1U, 4 Outlets, 1 Inlet)
Outlet Inlet
Voltage rating/current
rating
Socket type
(Socket)
Plug type
Socket type
(Socket)
Cable length
IEC60320 C13
NEMA L6-30P NEMA L6-30R 4.4m Rating: 250V 30A
(Normal usage rating:
24A)