1. ETERNUS DX Installation
This chapter provides the installation specification of the ETERNUS DX.
Installation Specifications
ETERNUS DX100 S4
Table 1 shows the installation specifications of the ETERNUS DX100 S4 and Table 2 shows the efficiency and the
power factor of the power supply unit.
Table 1 ETERNUS DX100 S4 Installation Specifications
Item ETERNUS DX100 S4
Dimensions
(W ´ D ´ H)
Controller enclosure 2.5" type
482 ´ 645 ´ 88mm (2U)
3.5" type
482 ´ 670 ´ 88mm (2U)
Drive enclosure 2.5" type
482 ´ 540 ´
88mm (2U)
3.5" type
482 ´ 560 ´ 88mm (2U)
High-density type
482 ´ 980 ´ 176mm (4U)
Power distribution unit (*1) 1U
435 ´ 148 ´
38mm (*2),
482 ´ 111 ´ 44mm (*3)
2U (*4)
(485 ´
280 ´ 43mm) ´ 2 (*5),
(485 ´ 123 ´ 44mm) ´ 2 (*6)
Maximum weight
(*7)
Controller enclosure 2.5" type 35kg
3.5" type 35kg
Drive enclosure 2.5" type 35kg
3.5" type 35kg
High-density type 100kg
Power distribution unit (*1) 1U 2.0kg (*2),
2.5kg (*3)
2U (*4)
(6.0kg) ´
2 (*5),
(3.0kg) ´ 2 (*6)
Power Voltage AC 100 – 120V, AC 200 – 240V
Phase Single
Frequency 50Hz/60Hz
7
FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems
Site Planning Guide
Copyright 2021 FUJITSU LIMITED
P3AM-7632-18ENZ0