EasyManua.ls Logo

Fujitsu ETERNUS DX100 S4 - ETERNUS DX Installation; Installation Specifications; Eternus Dx100 S4; Table 1 ETERNUS DX100 S4 Installation Specifications

Fujitsu ETERNUS DX100 S4
57 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1. ETERNUS DX Installation
This chapter provides the installation specification of the ETERNUS DX.
Installation Specifications
ETERNUS DX100 S4
Table 1 shows the installation specifications of the ETERNUS DX100 S4 and Table 2 shows the efficiency and the
power factor of the power supply unit.
Table 1 ETERNUS DX100 S4 Installation Specifications
Item ETERNUS DX100 S4
Dimensions
(W ´ D ´ H)
Controller enclosure 2.5" type
482 ´ 645 ´ 88mm (2U)
3.5" type
482 ´ 670 ´ 88mm (2U)
Drive enclosure 2.5" type
482 ´ 540 ´
88mm (2U)
3.5" type
482 ´ 560 ´ 88mm (2U)
High-density type
482 ´ 980 ´ 176mm (4U)
Power distribution unit (*1) 1U
435 ´ 148 ´
38mm (*2),
482 ´ 111 ´ 44mm (*3)
2U (*4)
(485 ´
280 ´ 43mm) ´ 2 (*5),
(485 ´ 123 ´ 44mm) ´ 2 (*6)
Maximum weight
(*7)
Controller enclosure 2.5" type 35kg
3.5" type 35kg
Drive enclosure 2.5" type 35kg
3.5" type 35kg
High-density type 100kg
Power distribution unit (*1) 1U 2.0kg (*2),
2.5kg (*3)
2U (*4)
(6.0kg) ´
2 (*5),
(3.0kg) ´ 2 (*6)
Power Voltage AC 100 – 120V, AC 200 – 240V
Phase Single
Frequency 50Hz/60Hz
7
FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems
Site Planning Guide
Copyright 2021 FUJITSU LIMITED
P3AM-7632-18ENZ0

Table of Contents

Other manuals for Fujitsu ETERNUS DX100 S4

Related product manuals