Item ETERNUS DX200 S3
Maximum heat
generation
(*7)
Controller enclosure 2.5" type AC 100 – 120V 3,000kJ/h
AC 200 – 240V 3,000kJ/h
3.5" type AC 100 – 120V 2,700kJ/h
AC 200 – 240V 2,700kJ/h
Drive enclosure 2.5" type AC 100 – 120V 1,600kJ/h
AC 200 – 240V 1,600kJ/h
3.5" type AC 100 – 120V 1,300kJ/h
AC 200 – 240V 1,300kJ/h
High-density type AC 100 – 120V 4,700kJ/h
AC 200 – 240V 4,700kJ/h
Maximum amount
of exhaust air
Controller enclosure 2.5" type
4.0m
3
/min
3.5" type
4.0m
3
/min
Drive enclosure 2.5" type
4.0m
3
/min
3.5" type
4.0m
3
/min
High-density type
12.0m
3
/min
Environmental con-
ditions
Temperature Operating 10 – 40°C
Not operating 0 – 50°C
Shipping -40 – 60°C
Temperature gradient 15°C/Hr or less
Humidity Operating 20 – 80%RH
Not operating 8 – 80%RH
Shipping 8 – 90%RH
Humidity gradient 30%/day or less
Maximum wet bulb temperature 29°C
Altitude above sea level 0 – 3,000m
Airborne dust
0.15mg/m
3
or less
Gas concentration tolerance level Cl
2
: 6.8ppb or less, H
2
S: 7.1ppb or less,
SO
2
: 37ppb or less,
NH
3
: 423.5ppb or less,
NO
2
: 52ppb or less, O
3
: 5ppb or less,
HCl: 6.6ppb or less, HF: 3.6ppb or less
Oil vapor
0.2mg/m
3
or less
Seawater (salt corrosion) If the ETERNUS DX is installed on the ocean
or premises within 0.5km from the coast,
necessary measures must be taken to pre-
vent salt corrosion.
Vibration limit Operating 400gal
Not operating 1,000gal
Noise emission
(*8)
Sound pressure level 49dB (A)
Sound power level 6.7B
1. ETERNUS DX Installation
Installation Specifications
17
FUJITSU Storage ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems
Site Planning Guide
Copyright 2021 FUJITSU LIMITED
P3AM-7632-18ENZ0