COMMISSIONING - 4
Fulton Ltd
Press enter and navigate to parameter 641, press enter and edit value to 1, press enter again
to save.
The LMV shoul
d now run speed standardisation procedure and the display should go back to.
Once speed standardisation is complete the value of paramete
r 641 should become 0 again if
the standardisation was successful, navigate back to parameter 641 to confirm this.
13.
Navigate to parameter group 400 used to set fuel air ratios by running the burner (manual
control), press enter and the run screen should be displayed.
Press enter again and the burner will now run through its pre-ig
nition phases as follows.
Phase -
Standby (stationary)
Phase -
Fan ramp up
(fan motor = ON, extra valve = ON)
Phase -
Traveling to pre-purge position
Phase -
Pre-purging
VSRT-IOMM-2019-1
Page 33