COMMISSIONING - 4
Fulton Ltd
Table 7-Steam Program for Siemens LMV3*
Par.No.
Parameter
Min Value
Max Value
Fulton Setting
Customer
223
Repetition limit pressure switch mini-gas
1
16
1
225
Gas: Pre-purge time
20s
60s
30s
226
Gas: Pre-ignition time
0.2s
60min
2s
227
Gas: Safetytime1(TSA1)
0.2s
10s
5s
229
Gas: time to respond topressurefaultsinTSA1
0.2s
9.8s
1.8s
230
Gas: Interval1
0.2s
60s
5s
231
Gas: Safetytime2(TSA2)
0.2s
10s
5s
232
Gas: Interval2
0.2s
60s
2.0s
233
Gas: Afterburn time
0.2s
60s
8s
234
Gas: Postpurge time
0.2s
108mi,
15s
237
Gas pressure switch-max/ POC
input 0=deactivated
1= pressure switch-max 2=
POC
1
2
2
239
Gas: Forced intermittent
operation
0=deactivated
1=activated
0
1
1
240
Gas: Repetition limit loss of flame
1
2
1
241
Gas: Execution leakage test
0=no leakage test 1=leakage
test on start-up 2=leakage
test on shutdown
3=leakage test on both
0
3
0
242
Gas: Leakage test evacuation time
0.2s
10s
3s
243
Gas: Leakage test time atm pressure
0.2s
60s
10s
244
Gas: Leakage test filling time
0.2s
10s
3s
245
Gas: Leakage test time gas pressure
0.2s
60s
10s
246
Gas: Waiting time gas shortage
0.2s
60s
10s
400
Ratio Curves
401
Ratio control curve fuel actuator
0
90
402
Ratio control curve air actuator
0
90
403
Ratio control curve VSD
20%
100%
500
Ratio Control
501
No-flame positions fuel
actuator
Index0=no-load position
Index1=pre-purge position
Index2=post-purge position
0
90
0
0
0
502
No-flame positions air
actuator Index0=no-load
position Index1=pre-purge
position Index2=post-purge
position
0
90
0
65
45
*Data is for reference purposes only. Fulton Companies is not responsible for this product, including (but not limited to) its accuracy, reliability, and safety. No
Fulton document should substitute for full review of documentation available from the product manufacturer.
+Out of Test Fire
Note: Customer settings should be recorded in the Customer column for reference.