APPENDIX - A
Fulton Ltd
Fuel
Requirements
(Pressure requirements at rated
input)
VSRT Model
VSRT-10
Fuel Usage at Rated Input
(Natural Gas)*
M
3
/hr
10.7
Fuel Usage at Rated Input
(Propane Gas)**
M
3
/hr
4.6
Min Gas Pressure (NG or
LPG)
mbar
19
Max Gas Pressure (NG or
LPG)
mbar
35
*m³/hr based on 40.1mJ/m³ Natural Gas (2016 Dukes Report)
** m³/hr based on 94mJ/m³ Propane
Electrical
Requirements
(Applies to <20ppm NO
x
standar
blower motor and control options
VSRT Model
VSRT-10
Electrical Supply*
volts
Ø
Hz
400
3
50
Control Voltage
Volts ac
110
IP Rating
54
Full Load Amps (FLA)
Amps
14.8
d
)
*Includes Burner fan motor, feedwater pump & standard control circuit.
Weights &
Water Volume
VSRT Model
VSRT-10
Dry Weight
kg
876
Operating Weight at
Normal Working Level
kg
1,232
Flooded Weight
kg
1,364
Water Volume at Normal
Working Level
Litres
356
VSRT Model
VSRT-10
Rated Input at High Fire
kW
120
Minimum Input at Low Fire
kW
30
Rated Output
Boiler
HP
kg/hr
kW
10
156
98
Capacities
(Applies to elevations up to
2,000 ft)