EasyManua.ls Logo

GE CB Watch 3 - Spring Rewind Time Alarms; Rewind Motor Current Measurement

GE CB Watch 3
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CB Watch 3 User Manual v6.3 - May 2019 Page 67 of 100
HMI: Measurements / Alarms
Figure 107 Motor run time alarms
Rewind motor current
The CBW3 can measure the current used by the spring rewinding motor (usually a DC
motor) in order to notice any change over time, possibly highlighting additional friction in
the spring mechanism requiring more torque or a problem with the motor itself.
Both the mean (average) motor current and the maximum motor current (peak inrush
current) are recorded and displayed in the HMI:
HMI: Measurements / Last closing results
Figure 108 Spring rewind motor current data
Rewind current alarm
An alarm can be set on the maximum inrush current value of the motor by setting a “Max
threshold” value.
HMI: Settings / Analog channels
Figure 109 Spring rewind motor current alarm threshold
The alarm is displayed when the threshold has been reached or exceeded: