4 INSTALLATION
4.1 TRANSPORT
The UPS is packaged on a pallet suitable for handling with
a forklift.
Pay attention to the centre of gravity.
The UPS must be moved in upright position.
Do not tilt cabinets more than +/- 10° during handling.
Move the UPS in it’s original package to the final
destination site.
Do not stack other packages on top: the upper side of the
cabinet could be damaged.
If the UPS has to be lifted by crane, use suitable carrying
belts taking note of the centre of gravity marked on the
package.
Take all necessary precautions to avoid damage to the
cabinet while hoisting the UPS.
Forklift
Crane
Fig. 4.1-1 UPS cabinets moving
NOTE !
Check for sufficient floor and elevator
loading capacity.
4.1.1 Dimensions and weight
Dimensions SitePro 60 kVA
(W x D x H)
S
P
_
0
6
0
_
S
7
_
U
P
S
d
i
m
e
n
s
i
o
n
_
G
E
_
0
1
800mm
1'450mm
57.08"
7
5
0
m
m
2
9
.
5
2
"
31.49"
750 x 800 x 1’450 mm
29,52 x 31,49 x 57,08 inches
Weight SitePro 60 kVA
UPS rating
Weight
Kg / lbs
Floor loading
kg /m
2
- lbs/sq.ft
SitePro 60 kVA 455 / 1004 759 / 156