Modifications reserved Pagina 26/90
OPM_SPE_XXX_60K_60K_7GB_V010.doc Operatine Manual SitePro 60 kVA
4.7 ELECTRICAL WIRING
WARNING !
UPS installation and connection must be performed by QUALIFIED SERVICE PERSONNEL
only.
Refer to the ā€œSafety prescriptions - Installationā€ described on Section 1.
4.7.1 Mains input connection
WARNING !
Ensure that the AC and DC external isolators are OFF and locked out to prevent their inadvertent
operation.
Do not apply power to the equipment prior to the commissioning by a qualified service engineer.
Before any other input connection, connect and check the earthing wire.
The mains input power connection can be common or separate for bypass supply and rectifier input,
depending on the electrical system provided by the customer.
Common input Rectifier & Bypass
The same power source is to be used for both bypass supply and rectifier input (input F3).
Bear in mind that when the mains fuses are opened there is a supply failure to the rectifier as well as t
o
the bypass and manual bypass switch.
In this case, the interconnection links BR1, BR2 and BR3 on the input terminals or bus
bars MUST REMAIN CONNECTED.
Separate input Rectifier & Bypass (recommended)
The bypass and rectifier use different power sources (F1 and F2 inputs).
In this case, when the rectifier-input fuses are opened, the automatic bypass and the manual bypass
are supplied by the other connection.
In this case, REMOVE the interconnection links BR1, BR2 and BR3 on the input terminals
or bus bars. See Fig. 4.8.3-2 and Fig. 4.8.4-2.
Separate input Rectifier & Bypass (recommended) Common input Rectifier & Bypass
Fig. 4.7.1-1 Separate input rectifier & bypass Fig. 4.7.1-2 Common input rectifier & bypass
1 = Rectifier
2 = Inverter
3 = Automatic Bypass
4 = Manual Bypass
5 = Mains input
6 = Load
7 = Battery