7.1 METERING MODE
The Metering mode is entered any time the metering button is pressed.
While in this mode the LCD will display a series of screens containing metering information.
In this mode the buttons perform the following functions:
metering scrolls forward to the next screen.
alarms abandons the Metering mode and enters the Alarms mode.
parameters abandons the Metering mode and enters the Parameters mode.
+ scrolls forward to the next screen.
– scrolls backward to the previous screen.
ok displays the main screen for this mode.
Main screen
This screen displays the current status of the UPS in a condensed form.
The information offered by this screen consists of:
• The type of the machine: family name, series number (P + unit number for parallel version from 1 to
8) and power range.
• The status of the load (referred to the most loaded phase - for RPA: respect to the rated power of
Parallel System).
• The estimated battery backup time in minutes with the present load.
SitePro S7 60kVA
LOAD ON INVERTER
LOAD = 50%
Autonomie = 12min
metering
alarms
parameters
+
ok
Battery data screen
This screen displays:
• The battery voltage.
• The battery current (negative values correspond to the discharge of the battery).
• The temperature of the battery (XXX indicates sensor disabled).
• The current charge level.
• The estimated backup time with the present load.
Ub=408V Ib= 5A
Battery Temp = + 25
°
C
Charge Level = 50%
Autonomy = 12min