Modifications reserved Pagina 86/90
OPM_SPE_XXX_60K_60K_7GB_V010.doc Operatine Manual SitePro 60 kVA
10.5.3 Remote Signalling Box (RSB)
The optional Remote Signalling Box allows monitoring of the operation of the UPS, using the potential
free contacts fitted on the “P4 - Customer Interface Board“ of the UPS.
It can be used by simply putting the box on a desktop or on a wall or, removing the box, it can be
surface mounted.
The remote panel contains an internal buzzer and the following status indicators:
Mimic diagram With LEDs indicating the operation of Rectifier and Inverter, and the
power source supplying the critical Load.
Alarm Indicating a critical situation on the UPS (LED light and audible alarm).
Stop Indicating the UPS is preparing to shut down in a short time.
Mute Push button, resets the buzzer.
Test Push button checks all the LEDs and the buzzer of the remote panel.
The cable connecting the RSB to the UPS cabinet must be min. 16 wires / 0.25mm
2
.
The plug B is included in the delivery of the option RSB (cable connecting UPS with RSB not included).
Maximal allowable length: 300 m (985 ft).
It must be wired at one end with a D - female plug- 25 pin (J2 – P4 Customer Interface Board).
NOTE !
The alarms on free potential contacts can be connected on terminals X1 instead J2 (see
correlation X1 – J2 in Section 9.1).
GE Digital Energy
P4 - Customer Interface
3123
1
3
2
4
5
J2 - SUB D - MALEB -
14
10
8
7
6
9
12
11
13
19
15
16
17
18
21
20
22
16
X3
22
23
19
20
17
g
130mm
5 1/4" in
X4
43
55
56
49
50
44
37
40
42
38
33
34
32
25
24
N
+
_
L
XB3
XB2
XB1
F50
IM6544
X15
SIGNALLING
A
1
2
REMOTE
max 300m / 985ft
216mm
8 1/2"
Mute Test
Alarm
Stop
SP_OPT_060_S7_RSB_01GB
CABLE TYPE
XY 16 x 0,25mm
A
3
i
n
7
7
mm
rosa + rosso
grigio + blu
C
XB
X1
17
6
J5
312 45
141312 15 16
J3
978 1110
2018 19 2221
JP3
X2
21
J4
J2
14
1
9
1
suitables only for XY standard cable
P.S.: The above mentioned colors are
TERMINALS
C
BLOCK
XB
BLOCK
TERMINALS
B
SUB D - MALE
J2
PLUG
STOP OPERATION
AUX. BUZZER
COMMON ALLARM
LOAD ON MAINS
LOAD ON INVERTER
UTILITY FAILURE
GND
24V
pink
red
grey
blue
white
brown
green
yellow
black
violet
grey/pink
blue/red
white/green
brown/green
white/yellow
yellow/brown
Fig. 10.5.2-1 Remote Signalling Box connection
A Terminals X3, X4 and X15 fitted inside the Remote Signalling Box.
B Plug J2 (sub D - male - 25 pin) must be connected to the connector J2 (sub D - female-25
pin) located on “P4 - Customer Interface Board“.
C Terminals block XB for 24 VDC / 1A supply Remote Signalling Box.
NOTE !
If the remote signal panel is plugged on connector J2, the terminal blocks X1 cannot be
used to drive an external alarms monitoring device, because it is supplied by the
internal UPS low voltage power supply.