OPM_SPE_XXX_60K_60K_7GB_V010.doc Operatine Manual SitePro 60 kVA
7.7.2 Messages list
Code Message Meaning
4002
WATCHDOG
RESET
The microprocessor has detected an incorrect operation:
transfers the load on mains and performs a program reset.
The inverter will restart automatically and will supply the load.
4111
RECTIFIER
MAINS OK
Rectifier input mains is again within the admitted tolerance
(voltage, frequency and phase).
4119
BATTERY TEST
STARTED
Start of manual or automatic battery test.
Rectifier output voltage is decreased to the value defined by
parameters.
4120
BATTERY TEST
STOPPED
End of manual or automatic battery test.
Rectifier output voltage is restored to floating voltage.
4161
RECTIFIER
ON
Rectifier received the command to switch ON.
4162
RECTIFIER
OFF
Rectifier received the command to switch OFF for:
input mains out of tolerance / EPO / UDC max.
4163
GENERATOR
ON
Customer interface (X1 - 11, 22) received a Gen-set ON signal.
Operating mode depend on setting of parameters.
4164
GENERATOR
OFF
Customer interface (X1 - 11, 22) received a Gen-set OFF signal.
Function Bypass enabled depends on setting of respective
parameter.
4302
INVERTER
CANNOT BE
TURNED ON
Inverter cannot be switched on because one of the following
conditions is still present:
- Overtemperature.
- Low battery voltage.
- Inverter fuses.
- Overload.
- K7 opening failure.
- High battery voltage.
- DC low.
- EPO.
4303
INVERTER
CANNOT BE
TURNEDOFF
Inverter cannot be switched OFF, because the load cannot be
switched to mains (voltage out of tolerance, not synchrony, BP
blocked).
4361
INVERTER
ON
The command to start the inverter has been activated on the
control panel.
4362
INVERTER
OFF
The command to switch OFF the inverter has been activated by
the control panel or automatically for alarm presence.
4411
BYPASS MAINS
OK
Bypass input mains is again within tolerance (voltage,
frequency and phase).
4500
COMMAND
LOAD OFF
Disconnection of the load by opening K6 and K7 for:
EPO / Load Off / Overload / Stop operation
4521
NO BYPASS
POWER
With the load supplied by electronic bypass, a mains failure or
K6 opening occurred.
4534
MULTIPLE LOAD
TRANSFER
2 transfers inverter- mains has been detected in a short time,
defined by parameter (default 30 sec.).
4535
BYPASS
LOCKED
Bypass to mains not enabled due to settings of parameters.
Contactor K6 is open.
4536
BYPASS
FREE
Settings of parameters enable Bypass transfer on mains.
Contactor K6 can be closed.