Modifications reserved Pagina 61/90
OPM_SPE_XXX_60K_60K_7GB_V010.doc Operatine Manual SitePro 60 kVA
Code Message Meaning
4561
LOAD
OFF
Push-button “load off” on the UPS Control Panel has been
pressed, with the output circuit breaker Q1 closed.
4562
DETOUR
ON
The auxiliary contact indicates that manual bypass Q2 was
closed.
4564
DETOUR
OFF
The auxiliary contact indicates that manual bypass Q2 was
opened.
4567
COMMAND
LOAD ON MAINS
The control unit received a command to transfer the load on
mains.
4568
COMMAND
LOAD ON INVERTER
The control unit received a command to transfer the load on
inverter.
4572
NO MORE
OVERLOAD
End of the overload condition detected with alarm 4570.
4580
INVERTER AND
MAINS
SYNCHRONIZED
The voltages of Inverter and mains bypass are synchronised.
4582
COMMAND
NOT TO
SYNCHRONIZE
Command not to synchronise with mains has been done for
mains BP out of tolerance (4410) or setting parameters.
4583
COMMAND TO
SYNCHRONIZE
Command to synchronise with mains has been done for mains
BP OK (4411) or setting parameters.
4600
COMMAND
UPS ON
The SEM mode function has been disabled or the programmed
time is expired.
The UPS returns to VFI mode supplying the load normally by
inverter.
4601
COMMAND UPS
STAND BY
The function SEM mode is enabled, and according to the time
program the UPS will run in SEM mode, supplying the load
normally by mains.
4602
Q1
OPEN
The auxiliary contact indicates that the output switch Q1 was
opened.
4603
Q1
CLOSED
The auxiliary contact indicates that the output switch Q1 was
closed.
4699
BATTERY TEST
IMPOSSIBLE
Not possible to start battery test (is postponed):
- No mains rectifier or bypass
- Battery not fully charged
- Load is below 10% or above 80%.
4763
REMOTE CONTROL
ON
Inverter can be started or shutdown by remote control.
Commands source can be chosen depending on the value of
parameter (service only):
0 = Only local panel.
1 = Only serial port on CI.
2 = Both.
.
4764
REMOTE CONTROL
OFF
Inverter cannot be started or shutdown by remote control.
Commands source can be chosen depending on the value of
parameter (service only):
0 = Only local panel.
1 = Only serial port on CI.
2 = Both.