OPM_SPE_XXX_60K_60K_7GB_V010.doc Operatine Manual SitePro 60 kVA
10.5 CONNECTION FOR OPTIONS
WARNING !
The installation and cabling of the options must be performed by QUALIFIED
SERVICE PERSONNEL only.
MAKE SURE THAT THE UPS INSTALLATION IS COMPLETELY POWERED DOWN.
Refer to the āSafety prescriptions - Installationā described on Section 1.
10.5.1 Auxiliary Power Supply (APS) 24 VDC
PA = Auxiliary Power Supply 24 VDC XB = Terminals for connection
PA
OPT_APS_SP060 S7_01
XB
PA
N
L
-
+
+
-
N
C
_
+
L
N
M4x10
+
_
L
N
Fig. 10.5.1-1 Auxiliary Power Supply 24 VDC
Connection From To
Cable PA+ (black) PA - APS: PA+ Terminal: XB1 (+)
Cable PA- (grey) PA - APS: PA- Terminal: XB2 (-)
Cable PA-L (black) PA - APS: L Terminal: F50 (L)
Cable PA-N (grey) PA - APS: N Terminal: XB3 (N)
Cable PA-PE (yellow-green) PA - APS: PE UPS frame: PE (see Fig. 10.5.1-1)
NOTE !
Clamp the cables with the cable-ties.