7.7 EVENTS (ALARMS AND MESSAGES)
Each of the following listed events can be displayed on the LCD screen or on PC where the “PowerJump
Manager” or “PowerJump DataShield” is installed.
Alarms and Messages are differently specified because the alarms are indicating an abnormal
functioning of the UPS (which are additionally signalled with the LED alarm and acoustically with the
buzzer), while the messages indicate the various states of operation of the UPS (stored in the events list,
but not activating the LED alarm and the buzzer).
When in the alarms mode, the LCD screen displays a time ordered sequence of screens corresponding
to the last 256 alarms and messages, each screen indicating:
01.01.2005 12:45:07
NR=255 Status=4A61
4115: LOW
BATTERY VOLTAGE
metering
alarms
parameters
+
ok
1- The date and time when the event occurred.
2- The number of the event (255 = the most recent).
The standard code and the status word.
3- Code with an explicit text description of the events.
7.7.1 Alarms list
Code Alarms Meaning
4000
SETUP VALUES
LOST
Parameters are lost and have been replaced with default values.
4004
UPS
FAILURE
The master unit detected the slave unit missing on the
communication bus even though switch Q1 is still closed.
4104
BATTERY
FUSES
This function, when enabled on input programmable relays
(password required), warns the user about the external battery
fuses failure or MCB opening, signalled by NO free contact.
4106
RECTIFIER
TRANSFORMER
OVERTEMPERATURE
The temperature sensor inside the input transformer winding
indicates overtemperature. Only the alarm is given.
The rectifier, when in an Off state, cannot start as long as this
condition persists.
4110
RECTIFIER MAINS
OUT OF TOLERANCE
Rectifier input mains is out of tolerance (voltage, frequency or
phase).
4115
LOW BATTERY
VOLTAGE
The battery has been discharged and reached “stop operation”
time-out (default 3 minutes), and the inverter will be shut down.
It will restart automatically only when the battery has
recharged enough for a minimum runtime.
4116
HIGH BATTERY
VOLTAGE
Dangerous high UDC-Voltage.
Causes inverter shutdown.
Inverter restarts automatically after battery returns to normal
floating voltage.
4117
BATTERY
EARTH FAULT
A leakage current to earth has been detected on the DC circuit.
4118 BATTERY FAULT
During battery test the voltage falls under the critical level
(depending setting parameters).
Battery test is stopped.
4130
TURN ON RECT.
OR SHUTDOWN UPS
Rectifier and inverter are OFF.
The DC power supply is discharging the battery slowly.
Rectifier must be restarted or battery must be disconnected in
order to avoid damage.