86 PMCS Interface Toolkit
Screen Selected Description
7 - Per-Phase Minimums
• Vln a Min; Vln b Min: n/a when Voltage Mode is DELTA
• Vln c Min: n/a when Voltage Mode is DELTA or SINGLE
• Vln Avg Min: n/a when Voltage Mode is DELTA
• Vll ab Min
• Vll bc Min; Vll ca Min; Vll Avg Min: n/a when Voltage
Mode is SINGLE
• Ia Min; Ib Min
• Ic Min: n/a when Voltage Mode is SINGLE
• I Avg Min
8 - Per-Phase Maximums
• Vln a Max; Vln b Max : n/a when Voltage Mode is
DELTA
• Vln c Max: n/a when Voltage Mode is DELTA or SINGLE
• Vln Avg Max: n/a when Voltage Mode is DELTA
• Vll ab Max
• Vll bc Max; Vll ca Max; Vll Avg Max: n/a when Voltage
Mode is SINGLE
• Ia Max; Ib Max
• Ic Max: n/a when Voltage Mode is SINGLE
• I Avg Max
9 - Power & Amp Demand
• KW SWD; KVAR SWD; KVA SWD**
• KW PD; KVAR PD; KVA PD**
• KW Total; KVAR Total; KVA Total
10 - THD and K-Factor
• V1 THD; V2 THD; V3 THD: n/a when Source is n/a
• I1 THD; I2 THD; I3 THD; I4 THD: n/a when Source is n/a
• I1 K Factor; I2 K Factor; I3 K Factor; I4 K Factor: n/a
when Source is n/a
**NOTE: If the Sliding Demand Reset is initiated, or a SWD setup register is
changed, SWD values are “N/A” in the meter until the number of sub-intervals
specified in the #sub intervals setup register have expired. The 3D faceplate and
Tabular wizard will display 0 for these values during this state.