FP1500 Installation, Configuration and Commissioning Manual 27
Element 001 is called
[Write the name of the element]
[Upper Case Letters and Numbers]
Select the option you wish to change or go back
to continue with the other addresses.
Introduction and change of the location text
Element 001 is called
[Room 87- ]
[Lower case letters and numbers]
To make changes to the location text, press the
< 9 > key.
You can type in text in 3 ways: “upper case
letters and numbers”, “lower case letters and
numbers” and “words”.
Element 001 is called
[PL.2 _ ]
[Word 1] 0=Zone 1=Floor 2=Room
3=Corridor 4=Cupboard 5=Floor
Element 001 is called
[PL.2 _ CORRIDOR ]
[Word 1] 0=Zone 1=Floor 2=Room
3=Corridor 4=Cupboard 5=Floor
The selected option appears at the bottom of
the screen.
Letters and numbers: this enables the
introduction of the signs on each key and the
forward and back keys are activated.
E.g. To change the room number, press the
<BACK> button once to delete the number,
then press the desired number button.
The cursor “-“, (flashing), indicates the position
on the screen.
Words: this mode is the simplest way of
introducing text that is frequently repeated for
many locations. The control unit has a series of
pre-programmed words that can be selected
using the < 9 > key to advance down the list.
E.g. To change a word (Room) to a different
one (Corridor), select the Words Mode and
delete the word with the <BACK> key.
The cursor remains in position ready for the
introduction of the new text. To enter the word
CORRIDOR, press <3>
Changing the alarm thresholds (detector sensitivity)
It is possible to programme alternative threshold
or pre-alarm and alarm limit values for each
detector (smoke or heat) as long as the control
unit software has the variable sensitivity mode
enabled.
E.g. There is a detector on Loop 1, address 26,
that requires that, between 06:30 and 17:45 a
pre-alarm should be set to 50 and fire alarm to
65, whilst for the rest of the day the levels
should return to the default values (pre-alarm at
60 and fire alarm at 70)
1. Sensor Text
2. Zone
3. Events
4. Alarm Thresholds
Alarm (normal 70) : [065]
Pre-Alarm (normal 60) : [050]
How is it configured?
During the element configuration, press the
< 9 > key and select option 4 <Alarm
Thresholds>. This option is displayed for smoke
or heat sensors only.
The control unit requests the alternative level it
will use during the day period
(e g 6:30 to
4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Interlogix FP1500 and is the answer not in the manual?

GE Interlogix FP1500 Specifications

General IconGeneral
BrandGE
ModelInterlogix FP1500
CategoryFire Alarms
LanguageEnglish

Related product manuals