FP1500 Installation, Configuration and Commissioning Manual 50
7 TECHNICAL SPECIFICATIONS
Mechanical
specifications:
Enclosure 420 mm x 335 mm x 110 mm
6.2 Kg without batteries
Cable input holes:
10 x 20 mm top; 10 x 20 mm inside.
Environmental:
Temperature: -5°C to +40°C
Relative Humidity: 95% maximum without condensation.
Protection index IP30
Supports conditions: 3K5 of the CEI 721-3-3:1978
Loop outputs:
FP1500/1: 1 loop
FP1500/2: 2 loops
Maximum loop capacity. 125 analogue sensors + 125 analogue modules
Applicable local authority laws and requirements
must be respected where modules and detectors
are used on loops.
Loop output voltage:
From 26 VDC to 32 VDC
Maximum loop current 400 mA.
Maximum loop length. 2 km
Maximum loop resistance: 44 Ohm
Maximum loop capacity: 500 nF
Recommended cable KAL21A:
2 wire cable 1.5 mm² stranded and shielded
Impedance: 115 Ω
Maximum voltage: 1500 V
Isolating resistance: > 10000 Ω / Km
Conductor resistance: ≤ 13.3 Ω / Km
Working temperature: -20°C to +85°C
Baud Rate: 1024 Baud
Communication protocol: Proprietary
Sounder output: Number of outputs on
main board:
2 configurable outputs
Supervision: Open circuit and short-circuit.
End of line resistor: 4K7 1/4W.
Maximum output current: 250 mA each.
Output voltage: Standby: between –5 and –9 V
Activated: between 18 and 28 V (nominal 24 V)
Recommended cable: KAL21:
Stranded 2-wire cable 1.5 mm²
Conductor resistance: ≤ 13.3 Ω / Km
Working temperature: -20°C to +70°C
Relay Output: Voltage-free auxiliary
relays:
Number of relay outputs
on main board:
2 voltage-free outputs (contact C/NO/NC).
Maximum switching power
at contacts:
1 A, 30 VDC, Resistive