GFK-2993F 83
For public disclosure
6.2.5.3 Using the Modbus TCP Machine Adapter
The Modbus TCP Machine Adapter limits for each Field Agent platform are displayed in the following table.
Supported Configurations for Modbus TCP Machine Adapter
Update
Interval (ms)
MFA Max Configured and Published
4-Byte Variables
EFA Max Configured and Published
4-Byte Variables
1000-1999
100
100
2000-2999
200
200
3000-3999
300
300
4000-4999
400
400
5000
500
500
Note All variables read from the Server by a Machine Adapter are published. Since Modbus TCP Server does not feature a
Subscription capability like that found in other automation protocols (such as OPC UA Server), the Modbus TCP Machine
Adapter will publish all variables configured to be read each update interval.