6–22 EPM 2200 POWER METER – INSTRUCTION MANUAL
GE COMMUNICATOR PROGRAMMING OVERVIEW CHAPTER 6: USING THE METER
The fields and allowed entries are as follows:
Power and Energy Format
Power Scale: Unit, kilo (k), Mega (M), or auto
Energy Digits: 5, 6, 7, or 8
Energy Decimal Places: 0-6
Energy Scale: Unit, kilo (k), or Mega (M)
Example: Based on Selections (click Recalculate to view)
For Example: a reading for Digits: 8; Decimals: 3; Scale: k would be formatted:
00123.456k
Power Direction: View as Load
Demand Averaging
Averaging Method: Block or Rolling
Interval (Minutes): 5, 15, 30, or 60
Sub Interval (if Rolling is selected): 1-4
Auto Scroll: Click to Activate
Display Configuration:
•Click Values to be displayed.
NOTE
Note
You MUST have at least ONE Display Configuration value selected.
NOTE
Note
If incorrect values are entered on the Energy and Display screen the following message
appears: