configuration takes effect after the download is complete. To restore the default configuration at any time, from
the C
ONFIGURATION column, select the Restore Defaults cell then select All Settings.
In MiCOM S1 Agile, the DNP3.0 data is shown in three main folders, one folder each for the point configuration,
integer scaling and default variation (data format). The point configuration also includes screens for binary inputs,
binary outputs, counters and analogue input configuration.
If the device supports DNP Over Ethernet, the configuration related settings are done in the folder DNP Over
Ethernet.
3.3 IEC 60870-5-103 CONFIGURATION
To configure the device:
1.
Select the CONFIGURATION column and check that the Comms settings cell is set to Visible.
2. Select the COMMUNICATIONS column.
3. Move to the first cell down (RP1 protocol). This is a non-settable cell, which shows the chosen
communication protocol – in this case IEC 60870-5-103.
COMMUNICATIONS
RP1 Protocol
IEC 60870-5-103
4. Move down to the next cell (RP1 Addr
ess). This cell controls the IEC 60870-5-103 address of the IED. Up to 32
IEDs can be connected to one spur. It is therefore necessary for each IED to have a unique address so that
messages from the master control station are accepted by one IED only. IEC 60870-5-103 uses an integer
number between 0 and 254 for the address. It is important that no two IEDs have the same IEC 60870 5 103
address. The IEC 60870-5-103 address is then used by the master station to communicate with the IED.
COMMUNICATIONS
RP1 address
162
5. Move down to the next cell (RP1 Baud Rat
e). This cell controls the baud rate to be used. Two baud rates are
supported by the IED, 9600 bits/s and 19200 bits/s. Make sure that the baud rate selected on the
IED is the same as that set on the master station.
COMMUNICATIONS
RP1 Baud rate
9600 bits/s
6. Move down to the next cell (RP1 Meas P
eriod). The next cell down controls the period between
IEC 60870-5-103 measurements. The IEC 60870-5-103 protocol allows the IED to supply measurements at
regular intervals. The interval between measurements is controlled by this cell, and can be set between 1
and 60 seconds.
COMMUNICATIONS
RP1 Meas Period
30.00 s
7. If the optional fibre optic connectors are fitted, the RP1 PhysicalLink cell is visible. This cell contr
ols the
physical media used for the communication (Copper or Fibre optic).
P64x Chapter 5 - Configuration
P64x-TM-EN-1.3 91