EasyManua.ls Logo

GE P645

GE P645
592 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The CT requirements for low impedance REF protection are generally lower than those for differential protection.
As the line CT
s for low impedance REF protection are the same as those used for differential protection the
differential CT requirements cover both differential and low impedance REF applications.
The current transformer knee-point voltage requirements are based on the following default settings for
transformer REF protection; IS1 = 27 A (primary value at 300/1 CT Ratio), IS2 = 270 A (primary value at 300/1 CT
ratio), K1 = 0%, K2 = 150%.
The K dimensioning factor for the REF function is smaller than that for the transformer differential protection. Since
the highest K factor must be considered, the CT requirements for transformer differential must be considered.
5.2.6.1 CT REQUIREMENTS - ONE BREAKER APPLICATION
To achieve through-fault stability, the K dimensioning factor must comply with the following:
System Conditions K Kneepoint voltage (VK)
2I
n
< I
F
£ 64I
n
5 £ X/R £ 120
12
V
K
³ 12I
n
(R
CT
+ 2R
L
+ R
r
)
where:
V
K
= kneepoint v
oltage
K = CT dimensioning factor
I
n
= rated current
R
CT
= resistance of CT secondary winding
R
L
= Resistance of a single lead from device to current transformer
R
r
= resistance of any other protection devices sharing the current transformer
To ensure through-fault stability is achieved, the following ratios: should not exceed a maximum disparity of 7:1
V
K-HV
/ R
tot-HV
: V
K-TN1
/ R
tot-TN1
V
K-LV
/ R
tot-LV
: V
K-TN2
/ R
tot-TN2
V
K-TV
/ R
tot-TV
: V
K-TN3
/ R
tot-TN3
where:
V
K-HV
= Kneepoint voltage of CT at HV side
R
tot-HV
= Total burden connected to CT at HV side
V
K-LV
= Kneepoint voltage of CT at LV side
R
tot-LV
= Total burden connected to CT at LV side
V
K-TV
= Kneepoint voltage of CT at TV side
R
tot-TV
= Total burden connected to CT at TV side
V
K-TN1
= Kneepoint voltage of TN1 CT
R
tot-TN1
= Total burden connected to TN1 CT
V
K-TN2
= Kneepoint voltage of TN2 CT
R
tot-TN2
= Total burden connected to TN2 CT
V
K-TN3
= Kneepoint voltage of TN3 CT
R
tot-TN3
= Total burden connected to TN3 CT
This ensures that during a through-fault condition, the flux density in the CTs is not greatly different.
Chapter 8 - Restricted Earth Fault Protection P64x
182 P64x-TM-EN-1.3

Table of Contents

Related product manuals