EasyManua.ls Logo

GE P645

GE P645
592 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
This type of protection must be co-ordinated with any other overvoltage devices at other locations on the system.
Transformer
s can typically withstand a 110% overvoltage condition continuously. The withstand times for higher
overvoltages should be declared by the transformer manufacturer.
To prevent operation during earth faults, the element should operate from the phase-phase voltages. To achieve
this, you set V>1 Measur’t Mode to Phase-Phase and V>1 Operating Mode set to Three-phase. You should
typically set the overvoltage threshold V>1 Voltage Set to 100% - 120% of the nominal phasephase voltage. You
should also set the time delay to prevent unwanted tripping of the delayed overvoltage protection function due to
transient over voltages, which do not pose a risk to the transformer. A typical delay setting would be 1 s - 3 s, with
a longer delay being applied for lower voltage threshold settings.
The second stage can be used to provide instantaneous high-set over voltage protection. The typical threshold
setting to be applied, V>2 Voltage Set, would typically be 130 - 150% of the nominal phasephase voltage. For
instantaneous operation, you should set the time delay to 0 s.
If you select phase-to-neutral operation, take care to ensure that the element will grade with other protections
during earth faults, where the phase-neutral voltage can rise significantly.
This type of protection must be coordinated with any other overvoltage devices at other locations on the system.
P64x Chapter 11 - Voltage Protection Functions
P64x-TM-EN-1.3 243

Table of Contents

Related product manuals