47
4.4.1. SW.VER - Versione software
Acronym Scrolling message Password Description
SW.VER SOFTWARE VERSION INFO R
The parameter shows the version (major.minor) of the controller software.
Unit of measurement: -
Options: -
4.4.2. CODE - Identifying code of controller
Acronym Scrolling message Password Description
CODE INSTRUMENT ID CODE FOR SERIAL COMM INFO R
The parameter shows identifying code of the device for serial communication.
Unit of measurement:
-
Options: 0...247
4.4.3. ERROR - Main input error
Acronym Scrolling message Password Description
ERROR MAIN INPUT ERROR INFO R
The parameter shows error detected by the main input.
Unit of measurement:
-
Options: nonE = No error
Lou = Process variable (PV) is below lower scale limit
HIGH = Process variable (PV) is higher than upper scale limit
Err = PT100 in short circuit or input values below lower limit
(for example, TC with incorrect connection)
Sbr = Sensor break or input values higher than upper limit
4.4.4. SAP.C - SAP code
Acronym Scrolling message Password Description
SAP.C SAP ORDER CODE INFO R
The parameter shows the product number (Fxxxxxx).
Unit of measurement
: -
Options: -
4.4.5. SEr.n - Serial number of controller
Acronym Scrolling message Password Description
SEr.n SERIAL NUMBER INFO R
The parameter shows the serial number of the controller (number shown on data plate).
The serial number is displayed in the form yy.ww nnnn, where
yy
= last two digits of year of production
ww = week of production
nnnn = progressive in week of production
Unit of measurement: -
Options: -