58
4.6.6. BAND - Maximum deviation for HBB
Acronym Scrolling message Submenu Attributes
BAND HOLD BACK BAND VALUE PR.SPT R W
If the HBB function is enabled, the parameter shows and sets the maximum deviation allowed for PV compared to SV.
Unit of measurement:
°C, °F, % based on chosen scale
Options: 0...999
4.6.7. HBB.R - Enabling HBB during ramp
Acronym Scrolling message Submenu Attributes
HBB.R ENABLE HOLD BACK BAND DURING STEP RAMP PR.SPT R W
If the HBB function is enabled, the parameter enables and disables it during the step ramp time.
Unit of measurement:
-
Options: OFF = Disables HBB function during ramp time
On = Enables HBB function during ramp time
4.6.8. HBB.H - Enabling HBB during hold
Acronym Scrolling message Submenu Attributes
HBB.H ENABLE HOLD BACK BAND DURING STEP HOLD PR.SPT R W
If the HBB function is enabled, the parameter enables and disables it during hold in the step.
Unit of measurement:
-
Options: OFF = Disables HBB function during hold in step
On = Enables HBB function during hold in step
4.6.9. HBB2 - Enabling HBB with respect to I.SPR
Acronym Scrolling message Submenu Attributes
HBB2 HOLD BACK BAND FUNCTION REFERRED TO I.SPR INPUT PR.SPT R W
If the HBB function is enabled, the parameter enables and disables it with respect to the remote setpoint input, which
can be enabled on the MODE submenu, SP.REM parameter = On and submenu I.SPR, parameter F.SPr = SETP
When the function is enabled with respect to the remote setpoint, if deviation PV-SPR exceeds value BAND, the program
time base is stopped.
Unit of measurement:
-
Options: OFF = Disables HBB function with respect to remote setpoint input
On = Enables HBB function with respect to remote setpoint input
4.6.10. S.SP.EN - Enabling retransmission of setpoint
Acronym Scrolling message Submenu Attributes
S.SP.EN SUBDUED SETPOINT RETRANSMITTED ENABLE PR.SPT R W
The parameter enables and disables retransmission of the setpoint value to other slaved controllers.
The set point value is sent by configured analog output A1, OUT.AN submenu, parameter F.o.A1 = SLV.SP.
Unit of measurement:
-
Options: OFF = Disables retransmission
On = Enables retransmission
4. CONFIGURATION
Gefran 650/1250/1350 Temperature Controller – Abbreviated Manual
40524-04 Rev0

Table of Contents

Other manuals for gefran 650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran 650 and is the answer not in the manual?

gefran 650 Specifications

General IconGeneral
Brandgefran
Model650
CategoryTemperature Controller
LanguageEnglish

Related product manuals