ADV200 • Functions description and parameters list 183
removed within the set time, the drive will not indicate any alarm condition.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.63 4576 Condensation delay s UINT16 5 0 50 ERW FVS
Setting of delay time (in seconds) for activation of the Condensation state (IPA 6044) condition used to switch
from 0 to 1 after the Liquid temp mon (IPA 6042) parameter has dropped below Dew temperature (IPA 6032)
+ Dew temp offset off (IPA 6034)
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.64 4596 Overhumidity thr perc FLOAT 85.0 0.0 100 ERW FVS
Represents the threshold value, in % , at which the Overhumidity state (PAR 6046) output trips.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.65 4578 Overhumidity delay s UINT16 5 0 50 ERW FVS
Setting of delay time (in seconds) for activation of the Overhumidity state (IPA 6046) condition used to switch
from 0 to 1 after the Air humidity (IPA 6020) parameter has become higher than Overhumidity thr (IPA 4596).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.66 4598 HumTSensErr code UINT32 0 0 0 ER FVS
Error code of alarm [52] HumTempSensErr, which can be:
0x0: no error
0x1: communication error on humidity / temperature sensor
0x2: error on NTC temperature sensor for temperature of liquid owing into heatsink
0x3: the sum of both
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.67 4546 An inpLoss activity ENUM Warning 0 4 ERW FVS
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Setting of drive behavior if alarm [62] An inpLos trips.
This alarm indicates disconnection of the 0.1V..10.1V or KTY84 o 4..20mA signal for parameters IPA 1502
Analog inp 1 type, IPA 1552 Analog inp 2 type, IPA 1602 Analog inp 1X type and IPA 1652 Analog inp 2X
type.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.68 4548 An inpLoss holdoff ms UINT16 1000 0 30000 ERW FVS
Represents the time the alarm condition has to persist before the [62] An inpLoss alarm is actually generated.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.69 4568 An inpLoss code UINT32 0 0 0 ER FVS
Lets you specify which analog input has gone into error.
0x01 error on analog input 1 standard control board
0x02 error on analog input 2 standard control board
0x04 error on analog input 1 I/O expansion board
0x08 error on analog input 2 I/O expansion board
0x10 error on dedicated KTY84 input on EXP-SENS expansion boards
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.70 4700 Alarm dig sel 1 ENUM No alarm 0 62 ERW FVS