210 ADV200 • Messages
C-2 “ExtIO fault” Alarm
The drive may generate an “ExtIO fault” alarm for a series of reasons. At drive startup there may be problems
with conguration, associated with the EXP-FL-XCAN-ADV card or parameter settings. During the Cong
phase the alarm might depend on an SDO communication error. During the Control phase the HeartBeat or
NodeGuarding protocol might fail due to an interruption in the communication with the slave. An Emergency
message sent by the slave could generate the “ExtIO fault” alarm.
Each reason for the alarm can be identied by to the associated subcode.
The table below shows information about the subcodes and how to associate these with the cause of the
alarm, to enable troubleshooting and proper use of the system.
Subcode Description Remarks
0 0 BusLoss Loss of communication in the Operational state
1..51 1h..35h SDO error Error sending the SDO. See the SDO Configuration Table on appendix to identify
the object with the problem
200 0xC8 CAN error Internal hardware fault; if the problem cannot be solved, replace the regulation
card
202 0xCA Config error The number or I/Os in the slave module has changed. Check parameter 5482
External IO info. Save the parameters to store the current configuraiton.
203 0xCB Lost Messages TPDOs coming from the slave too frequently. Check that the slave meets CAN-
open specifications for TPDO sending times
204 0xCC Opt IO installed An optional internal I/O expansion card has been installed. The EXP-XCAN-ADV
card functions are not available.
255..65535 0xFF..0xFFFF Slave Emergency Emergency message sent by the slave.
If the alarm is due to an Emergency message sent by the slave, the subcode contains the error code (Error
code low and Error code Hi) of the message, while 4 of the 5 additional bytes in the message are shown by
parameter 5486 External IO Failcode.
Emergency message content:
Byte0 Byte1 Byte2 Byte3 Byte4 Byte5 Byte6 Byte7
Error code
Low
Error code Hi Error register Info 0 Info 1 Info 2 Info3 Info4
Subcode PAR 5486 External IO Failcode
See the slave manual for information about the meaning of the Emergency message.

Table of Contents

Other manuals for gefran ADV200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran ADV200 and is the answer not in the manual?

gefran ADV200 Specifications

General IconGeneral
Brandgefran
ModelADV200
CategoryInverter
LanguageEnglish

Related product manuals