Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.74 4720 Alm autoreset time s FLOAT 0.0 0.0 60.0 ERW FVS
Setting of the time interval that must pass before executing an automatic reset.
If no alarms are enabled the drive is set to restart.
If some alarms are still enabled the drive is set to execute a new attempt at automatic reset.
At each attempted reset a counter increases. If the limit set in the Alm autoreset number parameter is reached
the drive is set to make no more attempts at reset and waits for a user reset.
The counter is set to zero when an automatic reset or user reset is performed and no alarms are enabled.
If the parameter is 0 the function is disabled.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.75 4722 Alm autoreset number UINT16 20 0 100 ERW FVS
Setting of the maximum number of attempted automatic resets.