EasyManuals Logo

gefran ADV200 User Manual

gefran ADV200
308 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #185 background imageLoading...
Page #185 background image
ADV200 • Functions description and parameters list 185
58 Plc14 fault
59 Plc15 fault
60 Plc16 fault
61 UV Wng&Restart
62 An inpLoss
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.74 4720 Alm autoreset time s FLOAT 0.0 0.0 60.0 ERW FVS
Setting of the time interval that must pass before executing an automatic reset.
If no alarms are enabled the drive is set to restart.
If some alarms are still enabled the drive is set to execute a new attempt at automatic reset.
At each attempted reset a counter increases. If the limit set in the Alm autoreset number parameter is reached
the drive is set to make no more attempts at reset and waits for a user reset.
The counter is set to zero when an automatic reset or user reset is performed and no alarms are enabled.
If the parameter is 0 the function is disabled.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.75 4722 Alm autoreset number UINT16 20 0 100 ERW FVS
Setting of the maximum number of attempted automatic resets.

Table of Contents

Other manuals for gefran ADV200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran ADV200 and is the answer not in the manual?

gefran ADV200 Specifications

General IconGeneral
Brandgefran
ModelADV200
CategoryInverter
LanguageEnglish

Related product manuals