819XX_MAN_GRM-H_11-2022_ENG_pag. 18
GRS 2
GRS 3
GRM 1
LOAD 1
LOAD 2
LOAD 3
OPEN DELTA
L2
L1
L3
V
3/L2
2/T1
1/L1
2/T1
1/L1
CONTROLLER
+ -
PE
ANALOG OUPUT
0-20 / 4-20 mA
0-5 / 0-10 V
2/T1
1/L1
24V
SUPPLY
+
-
AL
GRM
1
A2
US
D13
A+
A-
A2
D17
AL
AL
19
18
17
16
14
13
11
15
12
L1
L2
L3
R1R2R3
FUSE
FUSE FUSE
FUSE
GG
3/A2
4/US
GRS
3
5/A1
6/A2
7/AL
8/AL
AL
3/A2
4/US
GRS
2
5/A1
6/A2
7/AL
8/AL
AL
Master device could be also
controlled by IO-Link
- GRM: 1: MASTER
- GRS 2/3 : SLAVE
- FIRING MODE: ZC, BF,
- TOTAL HB DIAGNOSTIC AVAILABLE
Connect in parallel AL output, necessary
for have an OR logic condition.
Always choose only GRS with diagnostic options.
-
FUSE : fast fuse, see fuse table
- FUSE GG : see Fuse section
GRP 2
GRP 3
GRM 1
LOAD 1
LOAD 2
LOAD 3
OPEN DELTA
L2
L1
L3
V
3/L2
2/T1
1/L1
2/T1
1/L1
CONTROLLER
+ -
PE
ANALOG OUPUT
0-20 / 4-20 mA
0-5 / 0-10 V
2/T1
1/L1
AL
24V
SUPPLY
+
-
A2
US
DI
A1
A2
A2
AL
9
8
6
5
3
7
4
GRP
3
A2
US
DI
A1
A2
A2
AL
9
8
6
5
3
7
4
GRP
2
AL AL
GRM
1
A2
US
D13
A+
A-
A2
D17
AL
AL
19
18
17
16
14
13
11
15
12
L1
L2
L3
R1R2R3
FUSE
FUSE FUSE
FUSE
GG
Master device could be also
controlled by IO-Link
- GRM: 1: MASTER
- GRP 2/3 : SLAVE
- FIRING MODE: ZC, BF,
- TOTAL AND PARTIAL HB DIAGNOSTIC
AVAILABLE for each single leg. On GRPs
set parameter Ut.V=0
- FUSE : fast fuse, see fuse table
- FUSE GG : see Fuse section
GRM MASTER + 2 GRS SLAVE FOR OPEN DELTA LOAD
GRM MASTER + 2 GRP SLAVE FOR OPEN DELTA LOAD