819XX_MAN_GRM-H_11-2022_ENG_pag. 27
Settings
5.1.1.1. Analog input type
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
tyP
Inputs Analog input
R/W
1
The parameter sets the type of analog input.
Options:
(*) full scale calibration only, activated by key
5.1.1.2. Analog input scale minimum limit
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
Lo.S
Inputs Analog input
R/W
s.p. 0.0
The parameter sets the analog input scale minimum limit. It can be used to recalibrate the analog
input or set a minimum power. Example, if Lo.S=10.0, when the 0..10V input is at 0V, the delivered
power will be 10.0%, at 10V it will be 100.0%. Intermediate values will be heated.
min...max: -100.0...+200.0
5.1.1.3. Analog input scale maximum limit
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
HI.S
Inputs Analog input
R/W
s.p. 100.0
The parameter sets the analog input scale maximum limit. It can be used to recalibrate the analog
input or set an upper power limit. Example, if HI.S=90.0, when the 0..10V input is at 10V, the power
delivered will be 90.0%, at 0V it will be 0.0%. The intermediate values will be heated.
min...max: Lo.S...+200.0
0 Input disabled
1 0...10V
2 0...5V
3 0...20mA
4 4...20mA
5 Potentiometer
6 Potentiometer with custom calibration (*)
5. PARAMETER DESCRIPTIONS
5.1. Inputs
5.1.1. Analog input
Available only for GRM-H-x-x-x-AN-x-x-x-x-x-x model